sim-freezer-004 · generated 2026-08-14T22:48
A minor deviation from the equipment baseline has been detected.
Recommendation: Review the explainable findings and continue monitoring. Plan a technical inspection if the deviation persists.
| Finding | Severity | Confidence | Explanation |
|---|---|---|---|
| INTERNAL TEMP RISING | MEDIUM | 80% | A gradual internal temperature rise of 0.23 °C per hour has been detected over the last 8.0 h of available data. |
| INTERNAL TEMP UNSTABLE | HIGH | 90% | Internal temperature variability is elevated at 1.64 °C. |
| COMPRESSOR TEMP STABLE | INFO | 95% | Compressor temperature trend is stable. |
| COMPRESSOR CURRENT STABLE | INFO | 95% | Compressor current trend is stable. |
| INTERNAL TEMP BASELINE OK | INFO | 95% | Internal temperature remains consistent with this equipment's baseline. Current average: -17.105 °C; baseline: -17.335 °C. |
| COMPRESSOR TEMP BASELINE OK | INFO | 95% | Compressor temperature remains consistent with this equipment's baseline. Current average: 42.014 °C; baseline: 42.223 °C. |
| COMPRESSOR CURRENT BASELINE OK | INFO | 95% | Compressor current remains consistent with this equipment's baseline. Current average: 1.201 A; baseline: 1.201 A. |
| EVAPORATOR DELTA BASELINE OK | INFO | 95% | The internal-to-evaporator temperature difference remains consistent with this equipment's baseline. |
| EVAPORATOR DELTA STABLE | INFO | 92% | Cooling temperature difference remains stable. |
| COOLING EFFORT BASELINE OK | INFO | 92% | Compressor thermal and electrical effort remain consistent with the equipment baseline. |
| SENSOR HEALTH OK | INFO | 95% | All monitored sensor signals are available, plausible and responsive. |