Critical degradation relative to the equipment baseline has been detected.
Equipment status
Everything is working normally.
Cooling, electrical load and sensor readings match the usual behavior of this equipment.
Why Sentinel reached this conclusion
Critical degradation relative to the equipment baseline has been detected.
One or more sensor signals are missing, frozen, implausible or changing too quickly to represent normal equipment behavior.
Technical findings
11INTERNAL TEMP STABLE
Internal temperature trend is stable.
-0.0037 °C/hINTERNAL TEMP STABILITY OK
Internal temperature variability remains within the provisional nominal range.
0.1899 °CCOMPRESSOR TEMP STABLE
Compressor temperature trend is stable.
0.8854 °C/hCOMPRESSOR CURRENT STABLE
Compressor current trend is stable.
-0.0007 A/hINTERNAL TEMP BASELINE OK
Internal temperature remains consistent with this equipment's baseline. Current average: -80.009 °C; baseline: -80.005 °C.
-0.0038 °CCOMPRESSOR TEMP BASELINE OK
Compressor temperature remains consistent with this equipment's baseline. Current average: 57.505 °C; baseline: 52.862 °C.
4.6431 °CCOMPRESSOR CURRENT BASELINE OK
Compressor current remains consistent with this equipment's baseline. Current average: 1.204 A; baseline: 1.208 A.
-0.0033 AEVAPORATOR DELTA BASELINE OK
The internal-to-evaporator temperature difference remains consistent with this equipment's baseline.
0.0 °CEVAPORATOR DELTA STABLE
Cooling temperature difference remains stable.
0.0 °CCOOLING EFFORT DRIFT
A moderate increase in compressor effort has been detected relative to this equipment's baseline.
4.6398 indexCOMPRESSOR TEMPERATURE C IMPOSSIBLE JUMP
Compressor temperature sensor changed by 27.918 °C between two consecutive measurements. The provisional maximum accepted jump is 15.000 °C.
27.9176 °CCurrent measurements
Temperature history
Normal behavior of this equipment
Health history
Health Score evolution
Brain timeline
Maintenance
Record a comparison between a Sentinel sensor and a traceable reference.
Sensor integrity is evaluated by Sentinel Brain from recent real measurements.
Database integrity and local storage are checked directly on this Sentinel node.
Create a ZIP containing configuration, databases, code, templates, logs and tests.
Download full backupRecorded reference comparisons
Alarms
Everything is clear.
Sentinel has no active alarm for this equipment.